## Hitachi ABB Power Grids XMC20 Multiservice-Multiplexer
Original release date: October 20, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-294-02)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-294-02)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-20-294-02)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 9.1**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Hitachi ABB Power Grids
* **Equipment:** XMC20 Multiservice-Multiplexer
* **Vulnerability:** Improper Authentication
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to
remotely take control of the product.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
Hitachi ABB Power Grids reports the vulnerability affects the following XMC20
Multiservice-Multiplexer products:
* XMC20 R4 using COGE5 versions older than co5ne_r1h07_12.esw
* XMC20 R6 using COGE5 versions older than co5ne_r2d14_03.esw
### 3.2 VULNERABILITY OVERVIEW
#### 3.2.1 [IMPROPER AUTHENTICATION
CWE-287](https://cwe.mitre.org/data/definitions/287.html)
A vulnerability exists in a specific library included in these products. An
attacker could exploit the vulnerability by sending a specially crafted
message to the XMC20 node to open a communication channel without first
performing authentication, resulting in unauthorized access.
[CVE-2018-10933](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-10933)
has been assigned to this vulnerability. A CVSS v3 base score of 9.1 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Energy Sector
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Switzerland
### 3.4 RESEARCHER
Hitachi ABB Power Grids reported this vulnerability to CISA.
## 4\. MITIGATIONS
Hitachi ABB Power Grids has corrected the problem in the following product
versions and recommends users apply the firmware update at the earliest
availability:
* XMC20 R4: COGE5 Version co5ne_r1h07_12.esw (and newer)
* XMC20 R6: COGE5 Version co5ne_r2d14_03.esw (and newer)
For additional information and support please contact a product provider or a
[Hitachi ABB Power Grids service organization](https://www.hitachiabb-
powergrids.com/contact-us/).
Hitachi ABB Power Grids published cybersecurity advisory [PGVU-PGGA-
XMC20-2020034](https://search.abb.com/library/Download.aspx?DocumentID=9AKK107991A2862&LanguageCode=en&DocumentPartId=&Action=Launch)
to give users more information about this issue.
Hitachi ABB Power Grids recommends the following cybersecurity practices:
* Physically protect process control systems from direct access by unauthorized personnel.
* Do not directly connect control systems to the Internet.
* Separate control systems from other networks by means of a firewall system that has a minimal number of ports exposed.
* Do not use control systems networks for Internet browsing, instant messaging, or receiving e-mails.
* Portable computers and removable storage media should be carefully scanned for viruses before they are connected to a control system.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.cisa.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.cisa.gov](https://www.us-cert.cisa.gov/ics). Several
recommended practices are available for reading and download, including
[Improving Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.cisa.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.cisa.gov](https://www.us-
cert.cisa.gov/ics) in the Technical Information Paper, [ICS-TIP-12-146-01B--
Targeted Cyber Intrusion Detection and Mitigation Strategies](https://www.us-
cert.gov/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.