# ICS Advisory (ICSA-19-227-01)
## Johnson Controls Metasys
Original release date: August 15, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-227-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-227-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2Ficsa-19-227-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 6.8**
* **ATTENTION:** Exploitable remotely
* **Vendor:** Johnson Controls
* **Equipment:** Metasys
* **Vulnerabilities:** Reusing a Nonce, Key Pair in Encryption; Use of Hard-coded Cryptographic Key
## 2\. RISK EVALUATION
Successful exploitation of these vulnerabilities could be leveraged by an
attacker to decrypt captured network traffic.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of Metasys building automation system are affected:
* Metasys system versions prior to 9.0
### 3.2 VULNERABILITY OVERVIEW
#### 3.2.1 [REUSING A NONCE, KEY PAIR IN ENCRYPTION
CWE-323](https://cwe.mitre.org/data/definitions/323.html)
Metasys ADS/ADX servers and NAE/NIE/NCE engines make use of a shared RSA key
pair for certain encryption operations involving the Site Management Portal
(SMP). An attacker with access to the shared RSA key pair could decrypt
captured network traffic between the Metasys ADS/ADX servers or NAE/NIE/NCE
engines and the connecting SMP user client.
[CVE-2019-7593](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-7593)
has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been
calculated; the CVSS vector string is
([AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:N)).
#### 3.2.2 [USE OF HARD-CODED CRYPTOGRAPHIC KEY
CWE-321](https://cwe.mitre.org/data/definitions/321.html)
Metasys ADS/ADX servers and NAE/NIE/NCE engines make use of a hardcoded RC2
key for certain encryption operations involving the Site Management Portal
(SMP). An attacker with access to the hardcoded RC2 key could decrypt captured
network traffic between the Metasys ADS/ADX servers or NAE/NIE/NCE engines and
the connecting SMP user client.
[CVE-2019-7594](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-7594)
has been assigned to this vulnerability. A CVSS v3 base score of 6.8 has been
calculated; the CVSS vector string is
([AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:H/PR:N/UI:R/S:U/C:H/I:H/A:N)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Critical Manufacturing
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Ireland
### 3.4 RESEARCHER
harpocrates.ghost@protonmail.com reported these vulnerabilities to Johnson
Controls.
## 4\. MITIGATIONS
Johnson Controls recommends the following:
* Users should upgrade to Version 9.0 or later and configure sites with trusted certificates.
* Further ICS security notices and product security guidance are located at the [Johnson Controls product security website](https://www.johnsoncontrols.com/cyber-solutions/security-advisories).
For questions concerning this product, contact [Johnson Controls Global
Product Security](https://www.johnsoncontrols.com/cyber-solutions); email:
[productsecurity@jci.com](mailto:productsecurity@jci.com).
CISA recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](https://www.us-cert.gov/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
CISA reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
CISA also provides a section for [control systems security recommended
practices](https://www.us-cert.gov/ics/recommended-practices) on the ICS
webpage on [us-cert.gov](https://www.us-cert.gov/ics). Several recommended
practices are available for reading and download, including [Improving
Industrial Control Systems Cybersecurity with Defense-in-Depth
Strategies](https://www.us-
cert.gov/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS webpage on us-cert.gov](https://www.us-cert.gov/ics) in
the Technical Information Paper, [ICS-TIP-12-146-01B--Targeted Cyber Intrusion
Detection and Mitigation Strategies](https://www.us-cert.gov/ics/tips/ICS-
TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to CISA for tracking
and correlation against other incidents.
No known public exploits specifically target these vulnerabilities. High skill
level is needed to exploit.
暂无评论