# ICS Advisory (ICSA-19-106-02)
## WAGO Series 750-88x and 750-87x
Original release date: April 16, 2019
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-106-02)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-106-02)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-19-106-02)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 9.8**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** WAGO
* **Equipment:** Series 750-88x and 750-87x
* **Vulnerability:** Use of Hard-coded Credentials
## 2\. RISK EVALUATION
This vulnerability allows a remote attacker to change the settings or alter
the programming of the device.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of Series 750-88x and 750-87x, programmable logic
controllers, are affected:
* Series 750-88x
* 750-330 firmware versions prior to FW14
* 750-352 firmware versions prior to FW14
* 750-829 firmware versions prior to FW14
* 750-831 firmware versions prior to FW14
* 750-852 firmware versions prior to FW14
* 750-880 firmware versions prior to FW14
* 750-881 firmware versions prior to FW14
* 750-882 firmware versions prior to FW14
* 750-884 firmware versions prior to FW14
* 750-885 firmware versions prior to FW14
* 750-889 firmware versions prior to FW14
* Series 750-87x
* 750-830 firmware versions prior to FW06
* 750-849 firmware versions prior to FW08
* 750-871 firmware versions prior to FW11
* 750-872 firmware versions prior to FW07
* 750-873 firmware versions prior to FW07
### 3.2 VULNERABILITY OVERVIEW
**3.2.1 [USE OF HARD-CODED CREDENTIALS
CWE-798](https://cwe.mitre.org/data/definitions/798.html)**
By exploiting the undocumented service access, it is possible to change the
settings of a device and access web-based management with administrator
privileges. An attacker can exploit this vulnerability to lock other users out
from the device or open closed network ports. It is also possible to use this
service access as an FTP user and exchange or delete the application.
[CVE-2019-10712](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2019-10712)
has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Commercial Facilities, Critical Manufacturing, Energy, Transportation Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** United States, Germany, Switzerland, Poland, China, India
### 3.4 RESEARCHER
Reported by Jorn Schneeweisz/Recurity Labs to CERT-Bund coordinated by
CERT@VDE with NCCIC.
## 4\. MITIGATIONS
WAGO released a security advisory available at:
<https://www.wago.com/de/download/public/Sicherheitshinweis-SA-
SYS-2019-001/SA-SYS-2019-001.pdf>
WAGO recommends updating to the newest firmware as listed above and taking the
following defensive measures:
* Restrict network access to the web server.
* Restrict network access to the device.
* Do not directly connect the device to the Internet.
CERT@VDE has published an advisory regarding this vulnerability at the
following location:
<https://cert.vde.com/en-us/advisories/vde-2019-008>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.
暂无评论