# ICS Advisory (ICSA-18-352-01)
## ABB GATE-E2
Original release date: December 18, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-352-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-352-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-352-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 9.8**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** ABB
* **Equipment:** GATE-E2
* **Vulnerabilities:** Missing Authentication for Critical Function, Cross-site Scripting
## 2\. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow unrestricted
access to the administrative telnet/web interface of the device, enabling
attackers to compromise the availability of the device, read or modify
registers and settings, or change the device configuration.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of the Gateway Ethernet devices used in Pluto Safety
PLC systems are affected:
* GATE-E1 (EOL 2013), and
* GATE-E2 (EOL OCT 2018).
### 3.2 VULNERABILITY OVERVIEW
**3.2.1 [MISSING AUTHENTICATION FOR CRITICAL FUNCTION
CWE-306](https://cwe.mitre.org/data/definitions/306.html)**
These devices do not allow authentication to be configured on administrative
telnet or web interfaces, which could enable various effects vectors,
including conducting device resets, reading or modifying registers, and
changing configuration settings such as IP addresses.
[CVE-2018-18995](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-18995)
has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H)).
**3.2.2 [IMPROPER NEUTRALIZATION OF INPUT DURING WEB PAGE GENERATION ('CROSS-
SITE SCRIPTING') CWE-79](https://cwe.mitre.org/data/definitions/79.html)**
Using the administrative web interface, an unauthenticated attacker can insert
an HTML/Javascript payload into any of the device properties, which may allow
an attacker to display/execute the payload in a visitor browser.
[CVE-2018-18997](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-18997)
has been assigned to this vulnerability. A CVSS v3 base score of 7.1 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:L](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:R/S:C/C:L/I:L/A:L)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS** : Critical Manufacturing
* **COUNTRIES/AREAS DEPLOYED** : Worldwide
* **COMPANY HEADQUARTERS LOCATION** : Sweden
### 3.4 RESEARCHER
Nelson Berg of Applied Risk reported these vulnerabilities to NCCIC.
## 4\. MITIGATIONS
ABB will not be releasing updated firmware, as both GATE-E1 and GATE-E2 have
reached end of life (EOL). ABB recommends implementing defense-in-depth
principles to minimize the risk that vulnerabilities are exploited.
* Separate control system networks from other networks using firewall and managed switches that have minimal number of ports exposed.
* Physically protect control system from unauthorized personnel.
* Portable computers and removable storage should be scanned for viruses before connected to control system.
For more information about these vulnerabilities, ABB has published advisories
ABBVU-EPPC-3099-SE-002 and ABBVU-EPPC-3099-SE-003 at the following location to
notify users of these problems and identify mitigating factors:
<https://new.abb.com/about/technology/cyber-security/alerts-and-notifications>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.