# ICS Advisory (ICSA-18-352-05)
## Siemens TIM 1531 IRC Modules
Original release date: December 18, 2018 | Last revised: September 25, 2020
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-352-05)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-352-05)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-352-05)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 10.0**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Siemens
* **Equipment:** TIM 1531 IRC
* **Vulnerability:** Missing Authentication for Critical Function
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability could allow an attacker to
perform arbitrary administrative operations.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of TIM 1531 IRC--a communication module for SIMATIC
S7-1500, S7-400, and S7-300 with SINAUT ST7--are affected:
* TIM 1531 IRC all versions prior to 2.0
### 3.2 VULNERABILITY OVERVIEW
### 3.2.1 [MISSING AUTHENTICATION FOR CRITICAL FUNCTION
CWE-306](https://cwe.mitre.org/data/definitions/306.html)
When the product is configured it is missing proper authentication on Port
102/TCP, which could allow an attacker to perform arbitrary administrative
operations.
[CVE-2018-13816](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-13816)
has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Germany
### 3.4 RESEARCHER
Siemens reported this vulnerability to NCCIC.
## 4\. MITIGATIONS
Siemens recommends upgrading to firmware v2.0, which can be downloaded from
the following link:
<https://support.industry.siemens.com/cs/ww/en/view/109762596>
Siemens has identified the following specific workarounds and mitigations
users can apply to reduce the risk:
* Restrict access to Port 102/TCP on TIM 1531 IRC to trusted IP addresses
* Update firmware to version v2.0 (and reload the TIM station from engineering)
For additional information see Siemens' security advisory SSA-982399 at the
following location:
<http://www.siemens.com/cert/en/cert-security-advisories.htm>
As a general security measure, Siemens strongly recommends protecting network
access to devices with appropriate mechanisms. In order to operate the devices
in a protected IT environment, Siemens recommends configuring the environment
according to Siemens' operational guidelines for industrial security and
following the recommendations in the product manuals.
<https://www.siemens.com/cert/operational-guidelines-industrial-security>
Additional information on Industrial Security by Siemens can be found at:
<https://www.siemens.com/Industrialsecurity>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.
暂无评论