# ICS Advisory (ICSA-18-263-02)
## Rockwell Automation RSLinx Classic
Original release date: September 20, 2018 | Last revised: October 10, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-263-02)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-263-02)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-263-02)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 10.0**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Rockwell Automation
* **Equipment:** RSLinx Classic
* **Vulnerabilities:** Stack-based Buffer Overflow, Heap-based Buffer Overflow, Resource Exhaustion
## 2\. RISK EVALUATION
Successful exploitation of these vulnerabilities could crash the device being
accessed or allow arbitrary code execution on the device.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of RSLinx Classic, a software platform that allows
Logix5000 Programmable Automation Controllers to connect to a wide variety of
Rockwell Software applications, are affected:
* RSLinx Classic Versions 4.00.01 and prior.
### 3.2 VULNERABILITY OVERVIEW
#### 3.2.1 [STACK-BASED BUFFER OVERFLOW
CWE-121](https://cwe.mitre.org/data/definitions/121.html)
This vulnerability may allow a remote threat actor to intentionally send a
malformed CIP packet to Port 44818, causing the software application to stop
responding and crash. This vulnerability also has the potential to exploit a
buffer overflow condition, which may allow the threat actor to remotely
execute arbitrary code.
[CVE-2018-14829](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-14829)
has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H)).
#### 3.2.2 [HEAP-BASED BUFFER OVERFLOW
CWE-122](https://cwe.mitre.org/data/definitions/122.html)
This vulnerability may allow a remote, unauthenticated threat actor to
intentionally send a malformed CIP packet to Port 44818, causing the RSLinx
Classic application to terminate. The user will need to manually restart the
software to regain functionality.
[CVE-2018-14821](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-14821)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
#### 3.2.3 [UNCONTROLLED RESOURCE CONSUMPTION ('RESOURCE EXHAUSTION')
CWE-400](https://cwe.mitre.org/data/definitions/400.html)
A remote, unauthenticated threat actor may intentionally send specially
crafted Ethernet/IP packets to Port 44818, causing the software application to
stop responding and crash. The user must restart the software to regain
functionality.
[CVE-2018-14827](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-14827)
has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H)).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Critical Manufacturing, Energy, Water and Wastewater Systems
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** United States
### 3.4 RESEARCHER
Rockwell Automation, working with Tenable and Younes Dragoni and Alessandro Di
Pinto of Nozomi Networks, reported these vulnerabilities to NCCIC.
## 4\. MITIGATIONS
Rockwell Automation has released a new version of the software that can found
at Rockwell Automation knowledgebase article KB 1075712 (login is required):
<https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1075712>
Rockwell Automation also reports that users can disable Port 44818 if it is
not utilized during system operation. For more details on how to disable the
port and for Rockwell Automation's general security guidelines, please visit
knowledgebase article KB 1075747 (login is required):
<https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1075747>
Please see Rockwell Automation's industrial security advisory at the following
location on their website for further details (login is required):
<https://rockwellautomation.custhelp.com/app/answers/detail/a_id/1075747>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.
暂无评论