# ICS Advisory (ICSA-18-172-01)
## Delta Electronics Delta Industrial Automation COMMGR
Original release date: June 21, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-172-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-172-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-172-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.3**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Delta Electronics
* **Equipment:** Delta Industrial Automation COMMGR
* **Vulnerability:** Stack-based Buffer Overflow
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability may allow remote code execution,
cause the application to crash, or cause a denial-of-service condition in the
application server.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of Delta Industrial Automation COMMGR, a communication
management software, and accompanying PLC simulators are affected:
* COMMGR Version 1.08 and prior.
* DVPSimulator EH2, EH3, ES2, SE, SS2
* AHSIM_5x0, AHSIM_5x1
### 3.2 VULNERABILITY OVERVIEW
### 3.2.1 [STACK-BASED BUFFER OVERFLOW
CWE-121](https://cwe.mitre.org/data/definitions/121.html)
The application utilizes a fixed-length stack buffer where an unverified
length value can be read from the network packets via a specific network port,
causing the buffer to be overwritten. This may allow remote code execution,
cause the application to crash, or result in a denial-of-service condition in
the application server.
[CVE-2018-10594](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-10594)
has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been
calculated; the CVSS vector string is
[(AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L)](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L).
### 3.3 BACKGROUND
* **CRITICAL INFRASTRUCTURE SECTORS:** Commercial Facilities, Communications, Critical Manufacturing, Energy, Healthcare and Public Health
* **COUNTRIES/AREAS DEPLOYED:** Worldwide
* **COMPANY HEADQUARTERS LOCATION:** Taiwan
### 3.4 RESEARCHER
An anonymous researcher working with Trend Micro's Zero Day Initiative
reported this vulnerability to NCCIC.
## 4\. MITIGATIONS
Delta Electronics has released COMMGR v1.09 to address this vulnerability and
recommends users upgrade. The updated version can be downloaded at:
[http://www.deltaww.com/Products/PluginWebUserControl/downloadCenterCounter.aspx?DID=2093&DocPath=1&hl=en-
USl](http://www.deltaww.com/Products/PluginWebUserControl/downloadCenterCounter.aspx?DID=2093&DocPath=1&hl=en-
US)
Delta Electronics also recommends affected users apply application whitelists
to allow only trusted communications via Ports 502 and 10002.
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they [are not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website ](/ics/)in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies.](/ics/tips/ICS-TIP-12-146-01B)
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
NCCIC also recommends that users take the following measures to protect
themselves from social engineering attacks:
* Do not click web links or open unsolicited attachments in email messages.
* Refer to [Recognizing and Avoiding Email Scams](/reading_room/emailscams_0905.pdf) for more information on avoiding email scams.
* Refer to [Avoiding Social Engineering and Phishing Attacks](/cas/tips/ST04-014.html) for more information on social engineering attacks.
No known public exploits specifically target this vulnerability.