# ICS Advisory (ICSA-18-137-03)
## Siemens SIMATIC S7-400 CPU (Update A)
Original release date: May 17, 2018 | Last revised: September 11, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-137-03)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-137-03)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-137-03)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.5**
* **ATTENTION** : Exploitable remotely/low skill level to exploit
* **Vendor** : Siemens
* **Equipment** : SINAMIC S7-400 CPU
* **Vulnerability** : Improper Input Validation
## 2\. UPDATE INFORMATION
This updated advisory is a follow-up to the original advisory titled
ICSA-18-137-03 Siemens SIMATIC S7-400 CPU that was published May 17, 2018, on
the NCCIC/ICS-CERT website.
## 3\. RISK EVALUATION
Successful exploitation of this vulnerability could cause a denial-of-service
condition of the CPU. The CPU will remain in DEFECT mode until a manual
restart is performed.
## 4\. TECHNICAL DETAILS
### 4.1 AFFECTED PRODUCTS
The following versions of SIMATIC S7-400, a CPU used for process controls, are
affected:
* SIMATIC S7-400 (incl. F) CPU all hardware versions prior to, including, hardware v4.0,
* SIMATIC S7-400 (incl. F) CPU hardware v5.0 with firmware versions prior to v5.2, and
* SIMATIC S7-400H CPU all hardware versions prior to v4.5
### 4.2 VULNERABILITY OVERVIEW
### 4.2.1 [IMPROPER INPUT VALIDATION
CWE-20](https://cwe.mitre.org/data/definitions/20.html)
The affected CPUs improperly validate S7 communication packets, which could
cause a denial-of-service condition of the CPU. The CPU will remain in DEFECT
mode until manual restart.
Successful exploitation requires an attacker to be able to send a specially
crafted S7 communication packet to a communication interface of the CPU. This
includes Ethernet, PROFIBUS, and multi-point interfaces (MPI). No user
interaction or privileges are required to exploit the security vulnerability.
This vulnerability could allow causing a denial-of-service condition of the
core functionality of the CPU, compromising the availability of the system.
[CVE-2018-4850](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-4850)
has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
### 4.3 BACKGROUND
* **Critical Infrastructure Sectors:** Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems
* **Countries/Areas Deployed:** Worldwide
* **Company Headquarters Location:** Germany
### 4.4 RESEARCHER
Siemens ProductCERT reported this vulnerability to NCCIC.
## 5\. MITIGATIONS
Siemens has released updates for several affected products and recommends
users update to the new version.
* SIMATIC S7-400 (incl. F) CPU all hardware versions prior to, and including, hardware v4.0: Upgrade to hardware v5.0 or newer.
<https://support.industry.siemens.com/cs/ww/en/view/109483507>
* SIMATIC S7-400 (incl. F) CPU hardware v5.0 with firmware versions prior to v5.2: Update to firmware v5.2 or newer.
<https://support.industry.siemens.com/cs/ww/en/view/109474827>
* SIMATIC S7-400H CPU all hardware versions prior to v4.5: Upgrade to hardware v6.0 or newer.
<https://support.industry.siemens.com/cs/ww/en/view/75407031>
**\--------- Begin Update A Part 1 of 1 --------**
Siemens has identified the following specific workarounds and mitigations that
users can apply to reduce the risk:
* Apply cell protection concept: <https://www.siemens.com/cert/operational-guidelines-industrial-security>
* Use VPN for protecting network communication between cells.
* Apply Defense-in-Depth: <https://www.siemens.com/cert/operational-guidelines-industrial-security>
**\--------- End Update A Part 1 of 1 --------**
As a general security measure, Siemens strongly recommends protecting network
access to devices with appropriate mechanisms. In order to run the devices in
a protected IT environment, Siemens specifically recommends users configure
the environment according to Siemens' [Operational Guidelines for Industrial
Security](https://www.siemens.com/content/dam/webassetpool/mam/tag-siemens-
com/smdb/digital-factory/industrial-
security/online/documents/whitepapers/en/operational-guidelines-industrial-
security-en.pdf) and follow the recommendations in the product manuals.
Additional information on industrial security by Siemens can be found at:
<https://www.siemens.com/industrialsecurity>
For more information on this vulnerability and associated software updates,
please see Siemens security advisory SSA-914382 on their website:
<https://www.siemens.com/cert/advisories>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as virtual private networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including[ Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.