# ICS Advisory (ICSA-18-128-01)
## Siemens Medium Voltage SINAMICS Products (Update A)
Original release date: May 08, 2018 | Last revised: October 09, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-128-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-128-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-128-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.5**
* **ATTENTION** : Exploitable remotely/low skill level to exploit
* **Vendor** : Siemens
* **Equipment** : Medium Voltage SINAMICS Products
* **Vulnerabilities** : Improper Input Validation
## 2\. UPDATE INFORMATION
This updated advisory is a follow-up to the original advisory titled
ICSA-18-128-01 Siemens Medium Voltage SINAMICS Products that was published May
10, 2018, on the NCCIC/ICS-CERT website.
## 3\. RISK EVALUATION
Successful exploitation of these vulnerabilities could result in a denial-of-
service condition, resulting in a manual restart of the affected devices.
## 4\. TECHNICAL DETAILS
### 4.1 AFFECTED PRODUCTS
Siemens reports that these vulnerabilities affect the following products:
* SINAMICS GH150 V4.7 w. PROFINET: All versions prior to V4.7 SP5 HF7,
* SINAMICS GL150 V4.7 w. PROFINET: All versions prior to V4.8 SP2,
* SINAMICS GM150 V4.7 w. PROFINET: All versions prior to V4.8 SP2,
* SINAMICS SL150 V4.7.0 w. PROFINET: All versions prior to V4.7 HF30,
* SINAMICS SL150 V4.7.4 w. PROFINET: All versions prior to V4.8 SP2,
* SINAMICS SL150 V4.7.5 w. PROFINET: All versions prior to V4.8 SP2,
* SINAMICS SM120 V4.7 w. PROFINET: All versions prior to V4.8 SP2, and
**\--------- Begin Update A Part 1 of 2 --------**
* SINAMICS GM150 v4.7 w. PROFINET: All versions prior to v4.7 HF31, and
* SIMOTION D4xx v4.4 for SINAMICS SM150i-2 w. PROFINET: All versions prior to v4.4 HF26
**\--------- End Update A Part 1 of 2 --------**
### 4.2 VULNERABILITY OVERVIEW
### 4.2.1 [IMPROPER INPUT VALIDATION
CWE-20](http://cwe.mitre.org/data/definitions/19.html)
Specially crafted packets sent to Port 161/UDP could cause a denial-of-service
condition. The affected devices must be restarted manually.
[CVE-2017-12741](https://nvd.nist.gov/vuln/detail/CVE-2017-12741) has been
assigned to this vulnerability. A CVSS v3 base score of 7.5 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
### 4.2.2 [IMPROPER INPUT VALIDATION
CWE-20](https://cwe.mitre.org/data/definitions/20.html)
Specially crafted PROFINET DCP broadcast packets could cause a denial-of-
service condition of affected products on a local Ethernet segment (Layer 2).
Human interaction is required to recover the systems. PROFIBUS interfaces are
not affected.
[CVE-2017-2680](https://nvd.nist.gov/vuln/detail/CVE-2017-2680) has been
assigned to this vulnerability. A CVSS v3 base score of 6.5 has been
calculated; the CVSS vector string is
([AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
### 4.3 BACKGROUND
* **Critical Infrastructure Sectors:** Chemical, Critical Manufacturing, Energy, Food and Agriculture, Water and Wastewater Systems
* **Countries/Areas Deployed:** Worldwide
* **Company Headquarters Location:** Germany
### 4.4 RESEARCHER
Siemens ProductCERT reported these vulnerabilities to NCCIC.
## 5\. MITIGATIONS
Siemens recommends users implement the following updates. These updates can be
obtained from a Siemens representative or via Siemens customer service.
* SINAMICS GH150 V4.7 w. PROFINET: Update to V4.7 SP5 HF7 or upgrade to V4.8 SP2,
* SINAMICS GL150 V4.7 w. PROFINET: Upgrade to V4.8 SP2,
* SINAMICS SL150 V4.7.0 w. PROFINET: Update to V4.7 HF30 or upgrade to V4.8 SP2,
* SINAMICS SL150 V4.7.4 w. PROFINET: Upgrade to V4.8 SP2,
* SINAMICS SL150 V4.7.5 w. PROFINET: Upgrade to V4.8 SP2, and
* SINAMICS SM120 V4.7 w. PROFINET: Upgrade to V4.8 SP2
**\--------- Begin Update A Part 2 of 2 --------**
* SINAMICS GM150 v4.7 w. PROFINET: Upgrade to v4.7 HF31 or v4.8 SP2, and
* SIMOTION D4xx v4.4 for SINAMICS SM150i-2 w. PROFINET: Update to v4.4 HF26
**\--------- End Update A Part 2 of 2 --------**
As a general security measure, Siemens strongly recommends protecting network
access to devices with appropriate mechanisms. In order to operate the devices
in a protected IT environment, Siemens recommends configuring the environment
according to Siemens' operational guidelines for Industrial Security
(Download: <https://www.siemens.com/cert/operational-guidelines-industrial-
security>), and following the recommendations in the product manuals.
Additional information on Industrial Security by Siemens can be found at:
<https://www.siemens.com/industrialsecurity>
For more information on these vulnerabilities and associated mitigation
practices, please see Siemens security advisory SSA-546832 on their website:
<https://www.siemens.com/cert/advisories>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of these vulnerabilities. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including[ Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the [ICS-CERT website](/ics/) in the Technical Information Paper,
[ICS-TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.
暂无评论