# ICS Advisory (ICSA-18-102-01)
## Yokogawa CENTUM and Exaopc
Original release date: April 12, 2018 | Last revised: April 13, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-102-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-102-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-102-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 6.5**
* **Vendor** : Yokogawa
* **Equipment** : CENTUM series and Exaopc
* **Vulnerability** : Permissions, Privileges, and Access Controls
## 2\. RISK EVALUATION
Successful exploitation of this vulnerability could allow a local attacker to
generate false system or process alarms, or block system or process alarm
displays.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of Yokogawa products are affected:
* CENTUM series
* CENTUM CS 1000 all versions,
* CENTUM CS 3000 versions R3.09.50 and prior,
* CENTUM CS 3000 Small versions R3.09.50 and prior,
* CENTUM VP versions R6.03.10 and prior,
* CENTUM VP Small versions R6.03.10 and prior,
* CENTUM VP Basic versions R6.03.10 and prior.
* Exaopc versions R3.75.00 and prior,
* B/M9000 CS all versions, and
* B/M9000 VP versions R8.01.01 and prior.
### 3.2 VULNERABILITY OVERVIEW
### 3.2.1 [PERMISSIONS, PRIVILEGES, AND ACCESS CONTROLS
CWE-264](https://cwe.mitre.org/data/definitions/264.html)
A weakness in access controls may allow a local attacker to exploit the
message management function of the system.
[CVE-2018-8838](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-8838)
has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been
calculated; the CVSS vector string is
([AV:L/AC:H/PR:L/UI:N/S:U/C:L/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:L/AC:H/PR:L/UI:N/S:U/C:L/I:H/A:H)).
### 3.3 BACKGROUND
* **Critical Infrastructure Sectors:** Critical Manufacturing, Energy, Food and Agriculture
* **Countries/Areas Deployed** : Worldwide
* **Company Headquarters Location:** Japan
### 3.4 RESEARCHER
Yokogawa, working with JPCERT, reported this vulnerability to NCCIC.
## 4\. MITIGATIONS
Yokogawa has produced the following mitigations for the affected products.
* CENTUM Series
* CENTUM CS 1000, CENTUM CS 3000, CENTUM CS 3000 Small - No updates will be provided as these products are at end of support. Yokogawa recommends that affected users upgrade to the latest CENTUM VP.
* CENTUM VP, CENTUM VP Small, CENTUM VP BASIC - affected users should update to version R5.04.B2 or R6.04.00.
* Exaopc - affected users should update to version R3.76.00
* B/M9000CS - The vulnerability does not exist in this product however, the existence of affected software on the same PC may affect alarms for this device.
* B/M9000 VP - The vulnerability does not exist in this product however, the existence of affected software on the same PC may affect alarms for this device.
Please see Yokogawa Security Advisory Report YSAR-18-0001 at the following
location for more information:
<https://web-material3.yokogawa.com/YSAR-18-0001-E.pdf>
NCCIC recommends that users take defensive measures to minimize the risk of
exploitation of this vulnerability. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including[ Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available in the ICS-CERT Technical Information Paper, [ICS-TIP-12-146-01B--
Targeted Cyber Intrusion Detection and Mitigation Strategies](/ics/tips/ICS-
TIP-12-146-01B), available for download from the [ICS-CERT website.](/ics/)
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability. This
vulnerability is not exploitable remotely. High skill level is needed to
exploit.