# ICS Advisory (ICSA-18-032-02)
## 3S-Smart Software Solutions GmbH CODESYS Web Server
Original release date: February 01, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-032-02)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-032-02)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-032-02)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
### **CVSS v3 9.8**
**ATTENTION:** Remotely exploitable/low skill level to exploit.
**Vendor:** 3S-Smart Software Solutions GmbH
**Equipment:** CODESYS Web Server
**Vulnerability:** Stack-based Buffer Overflow
## AFFECTED PRODUCTS
All Microsoft Windows (also WinCE) based CODESYS web servers running stand-
alone Version 2.3, or as part of the CODESYS runtime system running prior to
Version V1.1.9.19, are affected.
## IMPACT
Successful exploitation of this vulnerability could cause the device the
attacker is accessing to crash, resulting in a buffer overflow condition that
may allow remote code execution.
## MITIGATION
This vulnerability will be fixed by patch V.1.1.9.19 for the CODESYS V2.3 web
server for Windows. This will be part of the CODESYS setup V2.3.9.56. The
release of this security patch was made available on January 30, 2018.
Currently, 3S-Smart Software Solutions GmbH has not identified any workarounds
for this vulnerability.
In general, 3S-Smart Software Solutions GmbH recommends the following
defensive measures to reduce the risk of exploitation of this vulnerability:
* Use controllers and devices only in a protected environment to minimize network exposure and ensure they are not accessible from outside.
* Use firewalls to protect and separate the control system network from other networks.
* Use VPN (Virtual Private Networks) tunnels if remote access is required.
* Protect both development and control systems from unauthorized access (e.g., by means of the operating system).
* Protect both development and control system by using up-to-date virus detecting solutions.
For additional information regarding the CODESYS products, or about the
described vulnerability, please contact the 3S-Smart Software Solutions
support team at this location:
<https://www.codesys.com/support-training/codesys-support.html>
For additional information find the CODESYS Security update at the following
location:
<https://customers.codesys.com/fileadmin/data/customers/security/2018/Advisory2018-01_LCDS-282.pdf>
For more information and general recommendations for protecting machines and
manufacturing facilities, see the CODESYS Security whitepaper available at
this location:
<https://customers.codesys.com/fileadmin/data/customers/security/CODESYS-
Security-Whitepaper.pdf>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of these vulnerabilities. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies.](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf)
Additional mitigation guidance and recommended practices are publicly
available in the NCCIC Technical Information Paper, [ICS-TIP-12-146-01B--
Targeted Cyber Intrusion Detection and Mitigation Strategies](/ics/tips/ICS-
TIP-12-146-01B), that is available for download from the [ICS-CERT web
site](/ics/).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target this vulnerability.
## VULNERABILITY OVERVIEW
## [STACK-BASED BUFFER OVERFLOW
CWE-121](https://cwe.mitre.org/data/definitions/121.html)
A crafted request may cause a buffer overflow and could therefore execute
arbitrary code on the web server or lead to a denial-of-service condition due
to a crash in the web server.
[CVE-2018-5440](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-5440)
has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been
assigned; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H)).
## RESEARCHER
Zhu WenZhe of Istury IOT security lab reported this vulnerability to NCCIC.
## BACKGROUND
**Critical Infrastructure Sectors:** Critical Manufacturing, Energy
**Countries/Areas Deployed:** Worldwide
**Company Headquarters Location:** Kempten, Germany
暂无评论