# ICS Advisory (ICSA-18-030-02)
## Siemens TeleControl Server Basic
Original release date: January 30, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-030-02)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-030-02)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-030-02)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
### **CVSS v3 8.8**
**ATTENTION:** Remotely exploitable/low skill level to exploit.
**Vendor:** Siemens
**Equipment:** TeleControl Server Basic
**Vulnerabilities:** Authentication Bypass Using an Alternate Path or
Channel, Permissions, Privileges, and Access Controls, Resource Exhaustion
## AFFECTED PRODUCTS
The following versions of TeleControl Server Basic, a monitoring platform, are
affected:
* TeleControl Server Basic versions prior to V3.1
## IMPACT
Successful exploitation of these vulnerabilities could allow for escalation of
privileges to perform administrative actions.
## MITIGATION
Siemens recommends that users install the latest version of TeleControl Server
Basic which can be found at:
<https://support.industry.siemens.com/cs/ww/en/view/109755199>
Siemens has also identified other mitigations that affected users can take:
* If TeleControl Server Basic is operated in standalone mode, then users can close Port 8000/TCP on the Windows firewall to mitigate vulnerabilities CVE-2018-4835 and CVE-2018-4836.
* If TeleControl Server Basic is operated in redundancy mode, then users can use the Windows firewall to restrict access to Port 8000/TCP to the second TeleControl Server Basics' IP address to mitigate vulnerabilities CVE-2018-4835 and CVE-2018-4836.
* Users can use the Windows firewall to close Ports 80/TCP and 443/TCP to mitigate vulnerability CVE-2018-4837.
For more information on these vulnerabilities and more detailed mitigation
instructions, please see Siemens Security Advisory SSA-65145 at the following
location:
[http://www.siemens.com/cert/en/cert-security-advisories.htm (link is
external)](http://www.siemens.com/cert/en/cert-security-advisories.htm)
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of these vulnerabilities. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies.](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf)
Additional mitigation guidance and recommended practices are publicly
available in the NCCIC Technical Information Paper, [ICS-TIP-12-146-01B--
Targeted Cyber Intrusion Detection and Mitigation Strategies](/ics/tips/ICS-
TIP-12-146-01B), that is available for download from the [ICS-CERT web
site](/ics/).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.
## VULNERABILITY OVERVIEW
## [AUTHENTICATION BYPASS USING AN ALTERNATE PATH OR CHANNEL
CWE-288](https://cwe.mitre.org/data/definitions/288.html)
An attacker with network access to Port 8000/TCP could bypass the
authentication mechanism gaining access to limited information.
[CVE-2018-4835](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-4835)
has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been
assigned; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N)).
## [PERMISSIONS, PRIVILEGES, AND ACCESS CONTROLS
CWE-264](https://cwe.mitre.org/data/definitions/264.html)
An authenticated attacker with network access to Port 8000/TCP could escalate
privileges and perform administrative operations.
[CVE-2018-4836](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-4836)
has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been
assigned; the CVSS vector string is
([AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H)).
## [UNCONTROLLED RESOURCE CONSUMPTION ('RESOURCE EXHAUSTION')
CWE-400](https://cwe.mitre.org/data/definitions/400.html)
An attacker with access to the TeleControl Server Basic's webserver (Ports
80/TCP or 443/TCP) could cause a Denial-of-Service condition on the web
server. The remaining functionality of the TeleControl Server Basic is not
affected by the Denial-of-Service condition.
[CVE-2018-4837](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2017-4837)
has been assigned to this vulnerability. A CVSS v3 base score of 5.3 has been
assigned; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L)).
## RESEARCHER
Siemens ProductCERT reported the vulnerabilities to NCCIC.
## BACKGROUND
**Critical Infrastructure Sector:** Critical Manufacturing
**Countries/Areas Deployed:** Worldwide
**Company Headquarters Location:** Germany
暂无评论