# ICS Advisory (ICSA-18-018-01A)
## Siemens SIMATIC WinCC Add-On (Update A)
Original release date: January 18, 2018 | Last revised: February 27, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-018-01A)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-018-01A)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-018-01A)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
### **CVSS v3 9.8**
**ATTENTION:** Remotely exploitable/low skill level to exploit.
**Vendor:** Siemens
**Equipment:** SIMATIC WinCC Add-On
**Vulnerabilities:** Stack-based Buffer Overflow, Improper Input Validation,
Improper Restriction of Operations within the Bounds of a Memory Buffer,
Security Features, Improper Access Control.
## UPDATE INFORMATION
This updated advisory is a follow-up to the original advisory titled
ICSA-18-018-01 Siemens SIMATIC WinCC Add-On that was published January 18,
2018, on the NCCIC/ICS-CERT website.
## AFFECTED PRODUCTS
Siemens reports that the vulnerabilities affect the following versions of
SIMATIC WinCC Add-On:
* SIMATIC WinCC Add-On Historian CONNECT ALARM all versions prior to and including v5.x,
* SIMATIC WinCC Add-On PI CONNECT ALARM all versions prior to and including v2.x,
* SIMATIC WinCC Add-On PI CONNECT AUDIT TRAIL all versions prior to and including v1.x,
* SIMATIC WinCC Add-On PM-AGENT all versions prior to and including v5.x,
* SIMATIC WinCC Add-On PM-ANALYZE all versions prior to and including v7.x,
* SIMATIC WinCC Add-On PM-CONTROL all versions prior to and including v10.x,
* SIMATIC WinCC Add-On PM-MAINT all versions prior to and including v9.x,
* SIMATIC WinCC Add-On PM-OPEN EXPORT all versions prior to and including v7.x,
* SIMATIC WinCC Add-On PM-OPEN HOST-S all versions prior to and including v7.x,
* SIMATIC WinCC Add-On PM-OPEN IMPORT all versions prior to and including v6.x,
* SIMATIC WinCC Add-On PM-OPEN PI all versions prior to and including v7.x,
* SIMATIC WinCC Add-On PM-OPEN PV02 all versions prior to and including v1.x,
* SIMATIC WinCC Add-On PM-OPEN TCP/IP all versions prior to and including v8.x,
* SIMATIC WinCC Add-On PM-QUALITY all versions prior to and including v9.x,
* SIMATIC WinCC Add-On SICEMENT IT MIS all versions prior to and including v7.x, and
* SIMATIC WinCC Add-On SIPAPER IT MIS all versions prior to and including v7.x
## IMPACT
Successful exploitation of these vulnerabilities could allow remote code
execution or a denial of service condition.
## MITIGATION
Gemalto has released an updated installer and Siemens strongly encourages
users upgrade to the new installer as soon as possible. The new installer is
available at:
[https://supportportal.gemalto.com/csm/?id=kb_article&sys_id=a459d328dba207c8fe0aff3dbf9619ce](https://supportportal.gemalto.com/csm/?id=kb_article&sys_id=a459d328dba207c8fe0aff3dbf9619ce)
Siemens also advises that users configure the operational environment
according to Siemens' Operational Guidelines for Industrial Security:
<https://www.siemens.com/cert/operational-guidelines-industrial-security>
For more information on these vulnerabilities and more detailed mitigation
instructions, please see Siemens Security Advisory SSA-127490 at the following
location:
<http://www.siemens.com/cert/advisories>
NCCIC recommends users take defensive measures to minimize the risk of
exploitation of these vulnerabilities. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies.](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf)
Additional mitigation guidance and recommended practices are publicly
available in the NCCIC Technical Information Paper, [ICS-TIP-12-146-01B--
Targeted Cyber Intrusion Detection and Mitigation Strategies](/ics/tips/ICS-
TIP-12-146-01B), that is available for download from the [ICS-CERT
website](/ics/).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation against other incidents.
No known public exploits specifically target these vulnerabilities.
## VULNERABILITY OVERVIEW
## [STACK-BASED BUFFER OVERFLOW
CWE-121](https://cwe.mitre.org/data/definitions/121.html)
Malformed ASN1 streams in V2C and similar input files can be used to generate
stack-based buffer overflows. The vulnerability could allow arbitrary code
execution.
[CVE-2017-11496](https://nvd.nist.gov/vuln/detail/CVE-2017-11496) has been
assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned;
the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H)).
## [STACK-BASED BUFFER OVERFLOW
CWE-121](https://cwe.mitre.org/data/definitions/121.html)
Language packs containing malformed filenames could lead to a stack-based
buffer overflow. The vulnerability could allow arbitrary code execution.
[CVE-2017-11497](https://nvd.nist.gov/vuln/detail/CVE-2017-11497) has been
assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned;
the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H)).
## [IMPROPER INPUT VALIDATION
CWE-20](https://cwe.mitre.org/data/definitions/20.html)
Language pack (ZIP file) with invalid HTML files could lead to NULL pointer
access. The vulnerability could cause denial of service of the remote process.
[CVE-2017-11498](https://nvd.nist.gov/vuln/detail/CVE-2017-11498) has been
assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned;
the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
**\--------- Begin Update A Part 1 of 1 --------**
## [IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER
CWE-119](https://cwe.mitre.org/data/definitions/119.html)
A stack overflow flaw in the custom XML parser could allow remote denial of
service.
[CVE-2017-12818](https://nvd.nist.gov/vuln/detail/CVE-2017-12818) has been
assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned;
the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
## [SECURITY FEATURES
CWE-254](https://cwe.mitre.org/data/definitions/254.html)
Remote manipulation of the language pack updater could allow NTLM relay
attacks.
[CVE-2017-12819](https://nvd.nist.gov/vuln/detail/CVE-2017-12819) has been
assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned;
the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H)).
## [IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER
CWE-119](https://cwe.mitre.org/data/definitions/119.html)
Arbitrary memory read from controlled memory pointer could allow remote denial
of service.
[CVE-2017-12820](https://nvd.nist.gov/vuln/detail/CVE-2017-12820) has been
assigned to this vulnerability. A CVSS v3 base score of 7.5 has been assigned;
the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H)).
## [IMPROPER RESTRICTION OF OPERATIONS WITHIN THE BOUNDS OF A MEMORY BUFFER
CWE-119](https://cwe.mitre.org/data/definitions/119.html)
A memory corruption flaw could allow remote code execution.
[CVE-2017-12821](https://nvd.nist.gov/vuln/detail/CVE-2017-12821) has been
assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned;
the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H)).
## [IMPROPER ACCESS CONTROL
CWE-284](https://cwe.mitre.org/data/definitions/284.html)
The administrative interface can be remotely enabled and disabled without
authentication. This could increase the attack surface.
[CVE-2017-12822](https://nvd.nist.gov/vuln/detail/CVE-2017-12822) has been
assigned to this vulnerability. A CVSS v3 base score of 5.3 has been assigned;
the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N)).
**\--------- End Update A Part 1 of 1 ----------**
## RESEARCHER
Sergey Temnikov and Vladimir Dashchenko from Kaspersky Lab reported these
vulnerabilities to Siemens.
## BACKGROUND
**Critical Infrastructure Sectors:** Chemical, Energy, Food and Agriculture,
Water and Wastewater Systems.
**Countries/Areas Deployed:** Worldwide
**Company Headquarters Location:** Germany
暂无评论