# ICS Advisory (ICSA-18-151-01)
## Delta Industrial Automation DOPSoft
Original release date: May 31, 2018
[Print Document](javascript:window.print\(\);)
[Tweet](https://twitter.com/share?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-151-01)
[Like Me](https://www.facebook.com/sharer.php?u=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-151-01)
[Share](http://www.addthis.com/bookmark.php?url=https%3A%2F%2Fus-
cert.cisa.gov%2Fics%2Fadvisories%2FICSA-18-151-01)
### Legal Notice
All information products included in [https://us-cert.gov/ics](/ics) are
provided "as is" for informational purposes only. The Department of Homeland
Security (DHS) does not provide any warranties of any kind regarding any
information contained within. DHS does not endorse any commercial product or
service, referenced in this product or otherwise. Further dissemination of
this product is governed by the Traffic Light Protocol (TLP) marking in the
header. For more information about TLP, see [https://www.us-
cert.gov/tlp/](/tlp/).
* * *
## 1\. EXECUTIVE SUMMARY
* **CVSS v3 7.3**
* **ATTENTION:** Exploitable remotely/low skill level to exploit
* **Vendor:** Delta Electronics
* **Equipment:** Delta Industrial Automation DOPSoft
* **Vulnerabilities:** Out-of-bounds Read, Heap-based Buffer Overflow, Stack-based Buffer Overflow
## 2\. RISK EVALUATION
Successful exploitation of these vulnerabilities could allow a remote attacker
to read sensitive information, execute arbitrary code, and/or crash the
application.
## 3\. TECHNICAL DETAILS
### 3.1 AFFECTED PRODUCTS
The following versions of DOPSoft, a Human Machine Interface (HMI) editing
software, are affected:
* DOPSoft Version 4.00.04 and prior.
### 3.2 VULNERABILITY OVERVIEW
#### 3.2.1 [OUT-OF-BOUNDS READ
CWE-125](https://cwe.mitre.org/data/definitions/125.html)
The application performs read operations on a memory buffer where the position
can be determined by a value read from a .dpa file. This may cause improper
restriction of operations within the bounds of the memory buffer, allow remote
code execution, alter the intended control flow, allow reading of sensitive
information, or cause the application to crash.
[CVE-2018-10623](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-10623)
has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L)).
#### **3.2.2[HEAP-BASED BUFFER OVERFLOW
CWE-122](https://cwe.mitre.org/data/definitions/122.html)**
The application utilizes a fixed-length heap buffer where a value larger than
the buffer can be read from a .dpa file into the buffer, causing the buffer to
be overwritten. This may allow remote code execution or cause the application
to crash.
[CVE-2018-10617](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-10617)
has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L)).
#### **3.2.3[STACK-BASED BUFFER OVERFLOW
CWE-121](https://cwe.mitre.org/data/definitions/121.html)**
The application utilizes a fixed-length stack buffer where a value larger than
the buffer can be read from a .dpa file into the buffer, causing the buffer to
be overwritten. This may allow remote code execution or cause the application
to crash.
[CVE-2018-10621](http://web.nvd.nist.gov/view/vuln/detail?vulnId=CVE-2018-10621)
has been assigned to this vulnerability. A CVSS v3 base score of 7.3 has been
calculated; the CVSS vector string is
([AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L](https://www.first.org/cvss/calculator/3.0#CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L)).
### 3.3 BACKGROUND
* **Critical Infrastructure Sectors:** Critical Manufacturing
* **Countries/Areas Deployed:** Worldwide
* **Company Headquarters Location:** Taiwan
### 3.4 RESEARCHER
B0nd @garagehackers working with Trend Micro's Zero Day Initiative reported
the vulnerabilities to NCCIC.
## 4\. MITIGATIONS
Delta Electronics recommends affected users update to the latest version found
at:
[http://www.deltaww.com/Products/PluginWebUserControl/downloadCenterCounter.aspx?DID=9063&DocPath=1&hl=en-
US](http://www.deltaww.com/Products/PluginWebUserControl/downloadCenterCounter.aspx?DID=9063&DocPath=1&hl=en-
US)
Delta Electronics also recommends affected users restrict the interaction with
the application to trusted files.
NCCIC recommends that users take defensive measures to minimize the risk of
exploitation of these vulnerabilities. Specifically, users should:
* Minimize network exposure for all control system devices and/or systems, and ensure that they are [not accessible from the Internet](/ics/alerts/ICS-ALERT-10-301-01).
* Locate control system networks and remote devices behind firewalls, and isolate them from the business network.
* When remote access is required, use secure methods, such as Virtual Private Networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize that VPN is only as secure as the connected devices.
NCCIC reminds organizations to perform proper impact analysis and risk
assessment prior to deploying defensive measures.
NCCIC also provides a section for [control systems security recommended
practices](/ics/content/recommended-practices) on the ICS-CERT web page.
Several recommended practices are available for reading and download,
including [Improving Industrial Control Systems Cybersecurity with Defense-in-
Depth Strategies](/sites/default/files/recommended_practices/NCCIC_ICS-
CERT_Defense_in_Depth_2016_S508C.pdf).
Additional mitigation guidance and recommended practices are publicly
available on the ICS-CERT website in the Technical Information Paper, [ICS-
TIP-12-146-01B--Targeted Cyber Intrusion Detection and Mitigation
Strategies](/ics/tips/ICS-TIP-12-146-01B).
Organizations observing any suspected malicious activity should follow their
established internal procedures and report their findings to NCCIC for
tracking and correlation to other incidents.
NCCIC also recommends that users take the following measures to protect
themselves from social engineering attacks:
* Do not click web links or open unsolicited attachments in email messages.
* Refer to [Recognizing and Avoiding Email Scams](/reading_room/emailscams_0905.pdf) for more information on avoiding email scams.
* Refer to [Avoiding Social Engineering and Phishing Attacks](/cas/tips/ST04-014.html) for more information on social engineering attacks.
No known public exploits specifically target these vulnerabilities.